Motor Protection
The electric motor is protected against power surges by means of a cut-out device, which is part of the star delta box.
A thermal trip switch avoids the electric motor overheating.
Settings for a 3-phase, alternating current motor
a) for on / off starter
rated current (A) according to motor specifications
b) for star delta starter
rated current (A) × 0,58 at 380 V and 50 Hz
rated current (A) × 0,58 at 220 V and 50 Hz
Testing
If a single phase is disconnected, the motor's fuse should blow after ca. 20 seconds (i.e. the contacter switches the motor off).